4.5 Sizing of Service and All Electric Homes
The minimum service entrance shall be 100 amperes with a 3-wire, 120/240 volt, single-phase
service with a grounded neutral. The nominal size of wire used with a 100 amp service shall be
No. 4 copper; for a 200 amp service, the nominal size shall be No. 2 copper.
The service entrance cable shall have the same rating (amperage) as the meter base and the
service equipment.
If the service entrance is to be replaced, a calculation of the usage or load within the dwelling
shall be completed to assist in determining the appropriate size. The service entrance shall be
properly sized for after Rehabilitation capacity. Room-by-room specifications noting electrical
outlets and fixtures shall be included in the scope of work. Nameplate ratings of all appliances
shall be reviewed for actual VA ratings. If the calculation falls at or near 100 amps, the service
shall be increased to 200 amps.
All Electric Homes: Homes equipped with all electric appliances shall be equipped with no less
than a 200 amp service.
Main Service Panel: Panels shall be in proper working condition with no evidence of
overheating, arcing, corrosion, or failure. The panel shall bear the UL label and shall be marked
as suitable for service equipment. Any panels identified as substandard by the U.S. Consumer
Product Safety Commission shall be replaced. Panels with evidence of malfunction or
deterioration shall be replaced.
4.6 Material and Equipment Installation
All materials, components, and equipment shall be listed or labeled by a qualified electrical
products testing laboratory such as “UL” or “CSA.”
Listed materials, components, and equipment shall be installed per the intended use and
location and per the manufacturer’s installation instructions.
4.7 Grounding
All electrical systems shall consist of a single phase 3-wire grounded neutral service entrance
and shall provide system grounding and equipment grounding protection.
The service panel shall be connected to the grounding electrode system and to an 8’ galvanized
or copper clad steel ground rod. All electrical panels shall meet the bonding requirements of
the National Electrical Code (NEC).
No comments:
Post a Comment